Hospital AHU Outdoor air Damper Actuator replacement; Belimo
Professor Butler HVAC
0:00 / 0:00
Hospital AHU Outdoor air Damper Actuator replacement; Belimo
1 512 просмотров · 4 мес. назад
Professor Butler HVAC
4,09 тыс. подписчиков
1 512 просмотров · 4 мес. назад
In this video I troubleshoot and replace a Belimo outdoor air damper actuator in a hospital environment. The customer reported the damper sticking, but the root cause wasn’t mechanical binding, it was the wrong actuator torque. The existing actuator was a 90 in‑lb model installed on a damper that required 180 in‑lb, so it couldn’t overcome the load.
I walk through:
• Identifying torque mismatch and verifying damper requirements
• Selecting the correct Belimo actuator based on torque and shaft size
• Proper mounting, linkage alignment, and anti‑rotation setup
• Travel verification and end‑stop adjustment
• Testing the actuator through the BAS to confirm smooth operation and correct outdoor air control
If you work in HVAC, controls, or hospital mechanical systems, this is a solid real‑world example of why actuator sizing matters.