How to Control a Mitsubishi E-800 Inverter Over CC-Link IE Field Basic Network
Valin Corporation
0:00 / 0:00
How to Control a Mitsubishi E-800 Inverter Over CC-Link IE Field Basic Network
4 035 просмотров · 1 год назад
Valin Corporation
6,42 тыс. подписчиков
4 035 просмотров · 1 год назад
Equipment used:
Inverter: Mitsubishi FR-E820S-0008EPA-60
Controller: Mitsubishi FX5U CPU
Switch: TP-Link TL SF-1005D
Software: GX Works3
Steps:
With the inverter in PU mode, set the following parameters: (0:38)
Pr.1429: 61450
Pr.1434 – Pr.1437: Inverter IP address
Pr.1449 – Pr.1452: PLC IP address
Power cycle the inverter and connect an ethernet cable. (5:37)
Open a new project in GX Works3. (7:12)
If needed, import the FR-E800 inverter profile (available here: https://www.cc-link.org/sch/C020?lang...) (8:17)
Configure the PLC Ethernet Port in Module Parameters: (8:49)
Set desired IP address and subnet mask
Use CC-Link IE Field Basic
In Network Configuration settings, drag an FR-E-800 inverter next to the CPU and check that its IP address matches the real inverter’s address
In Refresh settings, set up the remote device addressing
Check and apply the settings
Convert the program, write it to the PLC, and reset the PLC. (12:00)
Additional reference: https://www.mitsubishielectric.com/dl...
If you have any questions or are just looking for some help, we're happy to discuss your application with you. Reach out to us at (800) 774-5630 or visit https://www.valin.com.