How to Control a Mitsubishi E-800 Inverter Over CC-Link IE Field Basic Network

Valin Corporation

0:00 / 0:00

How to Control a Mitsubishi E-800 Inverter Over CC-Link IE Field Basic Network

4 035 просмотров · 1 год назад
Valin Corporation
6,42 тыс. подписчиков
4 035 просмотров · 1 год назад
Equipment used: Inverter: Mitsubishi FR-E820S-0008EPA-60 Controller: Mitsubishi FX5U CPU Switch: TP-Link TL SF-1005D Software: GX Works3 Steps: With the inverter in PU mode, set the following parameters: (0:38) Pr.1429: 61450 Pr.1434 – Pr.1437: Inverter IP address Pr.1449 – Pr.1452: PLC IP address Power cycle the inverter and connect an ethernet cable. (5:37) Open a new project in GX Works3. (7:12) If needed, import the FR-E800 inverter profile (available here: https://www.cc-link.org/sch/C020?lang...) (8:17) Configure the PLC Ethernet Port in Module Parameters: (8:49) Set desired IP address and subnet mask Use CC-Link IE Field Basic In Network Configuration settings, drag an FR-E-800 inverter next to the CPU and check that its IP address matches the real inverter’s address In Refresh settings, set up the remote device addressing Check and apply the settings Convert the program, write it to the PLC, and reset the PLC. (12:00) Additional reference: https://www.mitsubishielectric.com/dl... If you have any questions or are just looking for some help, we're happy to discuss your application with you. Reach out to us at (800) 774-5630 or visit https://www.valin.com.