How to Configuration Schneider Altivar Machine ATV320 VFD Setting #schneider #electrical #vfd #video
Power Plant Info.🏭🏭
0:00 / 0:00
How to Configuration Schneider Altivar Machine ATV320 VFD Setting #schneider #electrical #vfd #video
159 просмотров · 9 месяцев назад
Power Plant Info.🏭🏭
4,36 тыс. подписчиков
159 просмотров · 9 месяцев назад
Configuring a Schneider Altivar 320 VFD involves accessing the CONF menu, setting motor parameters (power, voltage, etc.), defining start/stop (two or three-wire), and setting speed references (potentiometer, analog input, or keypad).
Key steps include setting the CTL menu for command (TER for terminals) and reference sources (e.g., AI3 for 4-20mA) and performing an autotune (in the SIN menu) for accurate motor performance. Always check safety guidelines and match drive settings to the motor's nameplate.
Basic Setup Steps
Access Configuration: From the main display (RDY), press Enter, scroll to CONF, and press Enter.
Motor Parameters (SIN Menu): Go to FUSte-SIN and input motor details (Power, Voltage, Current, Freq, Speed) from the motor's nameplate.
Control Mode (CTL Menu):
Navigate to CTL (Command Menu).
Set CHCF to SEP (Separate Ref/Cmd) for terminal control.
Set CD1 (Command Input) to TER (Terminals) for start/stop via physical inputs.
Speed Reference (CTL Menu):
Set FR1 (Freq Ref 1) to your desired source (e.g., AI3 for analog input).
For analog input scaling (e.g., 4-20mA), go to the I/O menu, select AI3-, and set CRL3 (min) and CRH3 (max).
2/3 Wire Control: In I/O - TCC, set to 2C (2-wire) or 3C (3-wire).
Autotune (SIN Menu):
Go to SIN - Tune.
Set TUNE to YES and press Enter to start; wait for motor noise.
Check status for "done" or "measure".
Acceleration/Deceleration: Adjust ACC (Accel) and DEC (Decel) times in the CTL menu.
Key Parameters to Know
CONF: Main Configuration Menu.
SIN: Simply Start Menu (Motor data, Autotune).
CTL: Control Menu (Command/Ref sources, Accel/Decel).
I/O: Inputs/Outputs Menu (Terminal functions, Analog scaling).
CHCF: Command/Freq Channel (SEP for separate control).
CD1: Command Active Channel (TER for terminals).
FR1: Frequency Reference 1 (e.g., AI3).
Tips
Press & Hold Enter: Hold Enter for ~3 seconds to save parameter changes.
Safety: Always follow local safety codes and disconnect power when wiring.
Check Motor Nameplate: Match motor specs (kW, V, A, Hz) to parameters for accurate performance