Перейти к содержимому

Configuring Danfoss VLT HVAC Basic FC-101 for Air handling unit (AHU) and FAN Application || digicon

DIGICON AUTOMATION

0:00 / 0:00

Configuring Danfoss VLT HVAC Basic FC-101 for Air handling unit (AHU) and FAN Application || digicon

51 263 просмотра · 6 лет назад
DIGICON AUTOMATION
5,83 тыс. подписчиков
51 263 просмотра · 6 лет назад
Configuring Danfoss VLT HVAC Basic FC-101 for Air handling unit (AHU) and FAN Application 1-01 MOTOR CONTROL PRINCIPAL [0] U/f 1-20 MOTOR kW AS PER MOTOR NAME PLATE 1-22 MOTOR VOLTAGE AS PER MOTOR NAME PLATE 1-23 MOTOR FREQUENCY AS PER MOTOR NAME PLATE 1-24 MOTOR CURRENT AS PER MOTOR NAME PLATE 1-25 MOTOR RPM AS PER MOTOR NAME PLATE 3-15 REFERENCE RESOURCE 1 AS PER REQUIREMENT 3-16 REFERENCE RESOURCE 2 0 3-41 ACCELERATION TIME 40 3-42 DECELERATION TIME 60 4-12 MOTOR SPEED LOW LIMIT 0 Hz 4-14 MOTOR SPEED HIGH LIMIT 50 Hz 5-10 TERMINAL 18 DIGITAL INPUT [8] START 5-11 TERMINAL 19 DIGITAL INPUT NO OPERATION 5-12 TERMINAL 27 DIGITAL INPUT NO OPERATION 5-13 TERMINAL 29 DIGITAL INPUT NO OPERATION 5-40 FUNCTION RELAY 0 [ 5 ] RUN 1 [ 9 ] ALARM