Mitsubishi Ductless Split Shut Off on OverCurrent Faults
The HVAC Hacker
0:00 / 0:00
Mitsubishi Ductless Split Shut Off on OverCurrent Faults
47 046 просмотров · 7 лет назад
The HVAC Hacker
33,8 тыс. подписчиков
47 046 просмотров · 7 лет назад
I am working on a Mitsubishi Ductless Split that has gone off twice on overcurrent. It turns out the days it went off on overcurrent. The days it went off on overcurrent the morning started off around 15*F. The compressor was trying to slug liquid refrigerant and lock restored till it locked out. I found the sw1 preheat control function was turned off so I activated it. This works like a crankcase heater.