CMMT-xx-EP x1 + ControlLogix + EthIP + Tel_910 + EPD + Step8 + RS5000 Single Parameter ReadWrite
Steven Proud
0:00 / 0:00
CMMT-xx-EP x1 + ControlLogix + EthIP + Tel_910 + EPD + Step8 + RS5000 Single Parameter ReadWrite
882 просмотра · 6 лет назад
Steven Proud
1,58 тыс. подписчиков
882 просмотра · 6 лет назад
Check out the link to sample code below!!
This video describes using Rockwell RS5000/LogixDesign software and explicit message (MSG) instructions to read or write individual parameters between an Allen Bradley PLC and CMMT series drive/motor controllers.
(0:00) Overview of Extended Process Data concepts discussed in previous videos of this series
(2:00) Review file "ApplicationNote_PTP_Drives_Rockwell.pdf" which discusses "Single Parameter Read/Write" concepts.
(4:30) RS5000/LogixDesign add MSG instruction and configure to READ data from PNU 2888.0 (parameter P0.10151.0.0)
(7:35) Review the table used to cross reference parameters (Festo document 8117800g1.pdf) to PNU's to allow configuration of the MSG instruction
(14:00) RS5000/LogixDesign download and test MSG instruction
(16:15) RS5000/LogixDesign add MSG instruction and configure to WRITE data to PNU 12325.0 (parameter P1.11280402.0.0)
(20:53) RS5000/LogixDesign discussion of write MSG instruction configuration bug between Rockwell and Festo CMMT
(24:10) RS5000/LogixDesign download and test project MSG instruction
There are some files (within a “zip” file) to accompany this video that can be retrieved at the following Google drive link:
https://drive.google.com/open?id=1vMr...