Cascading Condensate Clog Consequences: Service Call
ThermalTran Technical Training
0:00 / 0:00
Cascading Condensate Clog Consequences: Service Call
48 просмотров · 10 дн. назад
ThermalTran Technical Training
18 подписчиков
48 просмотров · 10 дн. назад
Walk-In Cooler Service Call: Severe Drain Clog Freezes Three Evaporators
In this video, we respond to a walk-in cooler with all three evaporators heavily iced and fans slinging water. We cover:
• Initial assessment of three evaporators on a single condensing unit with a KE2 Therm controller.
• Why we raised the temperature setpoint to 85 °F instead of initiating a standard defrost cycle.
• Melting the ice (and why the box temperature can drop slightly while ice is still absorbing heat)
• Propping the door open to accelerate melting
• Drain-line inspection: continuous flow into a mop sink, missing trap (design error), and a completely clogged main drain
• Isolating the manifold so we could pressure-flush the drain to daylight
• Cutting out and replacing the severely restricted section of drain line
• Reconnecting everything, restoring refrigeration, and reviewing/adjusting the KE2 Therm defrost settings (Time and frequency)
Chapters
0:00 – Intro & problem overview
0:30 – Initial inspection of iced evaporators
1:30 – Raising the KE2 Therm setpoint to force continuous defrost/melt
2:45 – Propping the door and observing melt behavior
3:30 – Drain-line evaluation and missing trap
5:00 – Locating and confirming the severe clog
6:15 – Isolating the manifold and pressure-flushing the drains
8:00 – Cutting out the clogged section
9:30 – Reconnecting drains, clearing remaining ice, and restoring refrigeration
10:45 – KE2 Therm defrost settings review and final notes
https://www.thermaltran.com
#WalkInCooler #Refrigeration #KE2Therm #DrainClog #EvaporatorIcing #HVAC #TechnicianTraining #ServiceCall